Direct Hot Surface Ignition SmartValve® Control. Slow Opening. Set 3.5" WC. 17 sec HSI Warm-Up. - 37163

HVAC/R & Hydronics
37163 MFG #: SV9510K2539/U
0.00000 /

The SmartValve® System Controls combine gas flow control and electronic direct main burner ignition sequencing functions into a single unit. The ignition source is 120V hot surface igniter lighting the main burner flame. Provides all gas ignition safety functions by controlling gas flow, ignition so

QTY
  • Features
  • Specifications
    • This system is suitable for a wide range of fan-assisted combustion, gas-fired appliances including furnaces, rooftop furnaces, boilers, unit heaters, infrared heaters, water heaters and commercial cooking appliances.
    • When controlled directly by a thermostat, the control does not provide a postpurge function, as power to the control is removed when the thermostat call for heat ends.
    • It can directly interface with the appropriate power supplies and a system thermostat for additional appliance applications.
    • The control communicates directly with the ST9160 Electronic Fan Timer (EFT) in typical forced warm air furnace applications.
  • Pressure Tapping: 1/8 in. - NPT
  • Capacity (m³/hr): Maximum at 1 in. P.D.--4.2 m³/hr; Maximum--5.7 m³/hr; Minimum--0.6 m³/hr
  • Capacity (ft³/hr): Maximum at 1 in. P.D.--150 ft³/hr; Maximum--200 ft³/hr; Minimum--20 ft³/hr
  • Pilot Gas Outlet: No
  • Inlet/Outlet Size (in.): 1/2 in. NPT x 1/2 in. NPT
  • Pressure Ratings (kPa): 3.5 kPa
  • Pressure Ratings (psi): 1/2 psi
  • Pressure Regulator Setting (kPa): 0.87 kPa
  • Pressure Regulator Setting (psi): 3.5 in. WC
  • Opening Characteristics: Slow
  • Body Pattern: Straight-through
  • Typical Ignition Hardware: Norton 271
  • Ignition Trial Time (sec): 9 sec
  • Ignition Trials To Lockout: 4 trials
  • Ignition Source: HSI
  • Flame Sense: HSI
  • Type of Gas: Natural (LP with included conversion kit)
  • Ignition Sequence: 17/27 sec
  • Ignition System Type: Direct Hot Surface Ignition
  • Ambient Temperature Range (C): -40 C to +79 C
  • Ambient Temperature Range (F): -40 F to +175 F
  • PrePurge: 15 seconds
  • Flame Failure Response Time (sec): 2 sec @ 5 µA
  • Tradeline Value: Universal
  • Approvals, Canadian Standards Association: CSA International: 112395
  • Frequency: 50 Hz; 60 Hz
  • Electrical Ratings: 24 Vac
  • Mounting: 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
  • Item Type: Product
  • Includes: LP Conversion Kit
  • Dimensions (mm): 81 mm wide x124 mm high x 104 mm long.
  • Dimensions (in.): 3.2 in. wide x 4.9 in. high x 4.1 in.long