• Features
  • Specifications
    • Includes spark cable adapters to allow field replacement of both Honeywell and competitive controls without replacing existing spark cable.
    • For use in single rod or dual rod/remote sense applications
    • For use with Natural or LP gas
    • Provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated. Ignition trial/delay sequence is repeated until the appliance lights or call for heat is removed.
    • Provides ignition sequencing, flame monitoring and safety shutoff for intermittent pilot warm air furnaces and heating appliances
    • Replaces over 400 White-Rogers, Robertshaw and Honeywell intermittent pilot ignition modules
  • Between Trial Time (sec): 5 minute delay after failed trial for ignition.
  • Typical Ignition Hardware: Q345, Q3451, Q3452
  • Maximum Valve Load @ 24 Vac (Amps): 1A Pilot, 2A Main @ 165 F; 1A Pilot, 1A Main @ 175 F
  • Ignition Trial Time (sec): 15 or 90 sec
  • Lockout Timing: continuous retry
  • Ignition Trials To Lockout: continuous retry
  • Ignition Source: Internal high voltage spark generator
  • Flame Sense: Single Rod or Two Rods
  • Type of Gas: Natural or LP
  • Typical Gas Control: VR8204, VR8304
  • Ignition Sequence: Continuous Retry
  • Ignition System Type: Intermittent Pilot
  • Ambient Temperature Range (C): -40 C to +74 C
  • Ambient Temperature Range (F): -40 F to +165 F
  • PrePurge: Configurable to 30 seconds or no prepurge
  • Flame Failure Response Time (sec): 2 seconds maximum
  • Tradeline Value: Tradeline
  • Approvals, Canadian Standards Association: Design Certified
  • Frequency: 60 Hz
  • Electrical Ratings: 24 Vac
  • Item Type: Product
  • Includes: Damper connection with automatic vent damper plug
  • Dimensions (mm): 100 mm high x 138 mm wide x 67 mm deep
  • Dimensions (in.): 3 15/16 in. high x 5 7/16 in. wide x 2 5/8 in. deep