• Features
  • Specifications
    • Non-volatile EPROM memory retains program settings during power outage
    • Boiler short cycling protection, boiler post purge and boiler shock prevention from cold water returning to boiler
    • Domestic hot water priority and priority override protection
    • Zoning Control for up to four zones or expanded to up to 64 zones with additional panels
    • Customizable control settings and schedules provide greater control and comfort and control up to two stages of heat from a single thermostat
    • Intuitive and accessible programming interface and central program of zone set points and setback programming
    • Displays outdoor temperature on all AQ1000 Series thermostats when used with an AQ12C10 outdoor sensor
  • Supply Voltage: 120V 60 Hz
  • Temperature Ratings (F): Panel--32 F to 130 F; Sensor-- -58 F to +230 F
  • Temperature Ratings (C): Panel--0 C to 55 C; Sensor-- -50 C to +110 C
  • Replacement Parts: AQ10X38 24 Vac 38 VA transformer,AQ12C11 supply/return/mixed loop sensor,AQ15740B 4-zone valve with end switch expansion module,AQ12C10 outdoor sensor,AQ15A00B boiler control module
  • Sensor: Supply/Return Sensor--10 kilohm NTC thermistor at 25 C (77 F) ±0.5F (±0.3C) up to 500 ft (150 M) using 18 AWG or larger wire, Lead Length: 10 ft. (3050 mm); Outdoor Sensor--10 kilohm NTC thermistor at 25 C (77 F) ± 0.5F (±0.3C) up to 500 ft (150 M) using
  • Operating Humidity Range (% RH): 5 to 90% RH, non-condensing
  • Electrical Connections: Wire-clamp screw terminals, Maximum 2 x 14 AWG each on line voltage terminals
  • Zone Output Contact Rating: Pumps: 120 Vac/250 Vac, 5A, 1/3 HP,Valves: 24 Vac, 0.5 A, 12 VA
  • Output Ratings: Boiler (T-T)-- 24 Vac, 0.5A, 12VA; Auxiliary Low Voltage-- 24 Vac, 0.5A, 12VA; Boiler Pump-- 120 Vac/250 Vac 5A, 1/3HP; DHW Pump/Valve-- 120 Vac/250 Vac 5A, 1/3HP; Auxiliary Pump-- Dry contact output, 120 Vac/250 Vac 5A, 1/3 HP
  • Zone Module Thermostat Input: Low voltage, Class II, 2-wire polarity-insensitive, digital communicating with power link to AQ1000 series thermostat.
  • B-B Communication Bus Terminals: Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to other Control or Zoning modules.
  • Demand Input: Heat Demand (Thermostat R-W), Auxiliary Demand, and DHW Demand--External dry contacts connection only
  • R-C Input (on Control and Zoning Modules): 24 Vac Class II (input on Control and Zoning Modules)
  • R-C Output (on transformer): 38 VA, 24 Vac Class II
  • Pump/Valve exercise: 30 seconds per 2 weeks of space heating inactivity
  • Boiler Heat Post Purge: Off, 10 seconds to 30 minutes (factory default is 30 seconds)
  • Boiler Control Temperature (C): Differential--1 C to 23 C or Auto (minimum 2 minutes on time)
  • Boiler Control Temperature (F): Differential--2 F to 41 F or Auto (minimum 2 minutes on time)
  • Zoning Devices Controlled: Zone valves with end switches
  • Number of Zones: 4
  • User Interface: LCD Display and a 7 button Key Pad,DIP Switches on zoning modules
  • Setback Program: 7 day, up to 2 setback periods/day.
  • Thermostat Compatibility: AQ1000 Series 2-wire communicating thermostats and most digital thermostats
  • Tradeline Value: Tradeline
  • Approvals, Canadian Standards Association: CSA C/US Certified to CSA and UL Standards, File No. LR76030
  • Weight (kg): 2.6 kg
  • Weight (lb): 5.7 lbs
  • Dimensions (mm): 42 cm wide x 20.3 cm high x 8.5 cm deep
  • Dimensions (in.): 16 1/2 in wide x 8 in. high x 3 3/8 in deep
  • Application: Boiler control for zoned hydronic systems